TM0098 Page 1 of 4 Issue 1.00
HOT WIRE TEST BOX
USER GUIDE
TM0098
WARNING
Please read this guide fully before attempting to operate the unit.
1.0 Introduction
This Guide describes the use of the Kidde Fire Protection Hot Wire Test Box (part number 1-53836-
K237) to test aspirating smoke detection systems. The unit provides 6V AC output from 220-240V AC
mains supply. High current at low voltage is passed through a cable in order to heat it, which causes
its insulation to burn giving off smoke. A timer is incorporated to provide a selectable burn period of
up to 3 minutes. The timer also helps to prevent the unit being inadvertently left on for an extended
period. The unit must never be left on unattended.
The unit must be operated for no more than three (3) minutes continuously and must be left off
immediately after operating for a period of at least six (6) minutes to allow it to cool.
The unit is protected against over-temperatures by a thermal switch. Once tripped, the thermal switch
will not allow operation for an extended period (up to an hour) regardless of power being present or
not. The thermal switch cannot be by-passed or reset manually.
Zobrazit stránku 0
1 2 3 4

Shrnutí obsahu

Strany 1 - USER GUIDE

TM0098 Page 1 of 4 Issue 1.00HOT WIRE TEST BOXUSER GUIDETM0098WARNINGPlease read this guide fully before attempting to operate the unit.1.0 Introducti

Strany 2 - 3.0 Equipment Set-Up

TM0098 Page 2 of 4 Issue 1.002.0 Preparation and PrecautionsWhen performing a hot wire test, ensure that all local standards, practices and regulatio

Strany 3 - 6.0 Smoke Test

TM0098 Page 3 of 4 Issue 1.00It is recommended that the accuracy of the burn period is confirmed using a stopwatch with the redindicator on the timer

Strany 4 - 9. Compliance

TM0098 Page 4 of 4 Issue 1.00The current to the wire is turned off automatically after the set period is complete. Smoke will havebeen generated and

Komentáře k této Příručce

Žádné komentáře